Venting Steam in Fluid Heating Processes
Call in the Auditors
By Steve Connor
With the current economic challenges, many facilities are looking for ways to reduce operating costs. Increasing the efficiency of a boiler or steam system can offer a fast and high return on investment.
Finding inefficiencies starts with a steam audit, which is a comprehensive analysis of energy used within a process, facility or equipment, including recommendations for energy-conservation measures. Reducing fuel cost is the number-one reason for a steam audit. Money saved on fuel can be reinvested in the business or, if needed, provide liquidity when cash flow is tight.
Types of Audits
There are two types of steam audits: a simple boiler room audit and a complete facility audit. In a simple audit, a professional evaluates the boiler room, including the boiler and accessory support equipment. In a complete site audit, auditors evaluate the boiler room, the steam system and all the components throughout the process and facility, such as steam traps, piping, valves and steam users.
Audit customers will be provided with:
- Data -- where and how a process, facility or equipment uses energy, along with costs and utility data affecting energy consumption.
- Analysis -- outlining suggested measures to make energy use more efficient, less expensive and more environmentally friendly.
- Final Report -- A detailed list of areas for improvement and recommended actions, usually accompanied by some type of economic justification.
A simple boiler system audit costs approximately $2,500 while a complete site audit, depending on the complexity and the size of the plant, can cost several thousand dollars.
Steam Audit Process
During a simple boiler room audit, facilities should operate as normal so the auditor can spot visual indications of energy loss and possible operational and safety issues.
The boiler, its controls, fuel delivery, blowdown (continuous and bottom), safety valves, safety valve piping, feedwater conditioning and delivery will be inspected to identify inefficiencies and possible hazards. This includes an inventory of key equipment, looking for energy-saving methods, areas to improve engineering practices and health and safety concerns.
Once this is completed, the auditor conducts a boiler efficiency analysis, sampling the products of combustion as the burner ramps from low to high fire. During this process, the auditor is looking for a typical boiler load and how much time the unit stays at certain firing rates. This, along with the flue gas analysis showing percent oxygen, carbon dioxide and carbon monoxide, will then determine the overall efficiency of the boiler. This is very important because a typical boiler will consume four times its initial cost in fuel, annually, and, in many industrial applications, this means a fuel cost in excess of $1 million per year.
In a complete facility audit, auditors also will focus on the boiler room but then extend beyond into the overall steam system looking for potential energy and safety improvements throughout. They will gather data regarding steam flow, pressures, temperatures, supply and return piping and support, steam trapping, steam venting, piping ancillaries including valving and insulation, remote condensate pumping and heat recovery. The point is to find energy savings by identifying where the losses or infractions are occurring, then documenting the data so it can be incorporated into the final report.
Important Steam Audit Findings
A simple boiler room audit or complete system review will determine the condition of the current boiler system. Both will look beyond age at issues such as:
- Pressure vessel condition.
- Evidence of overheating and poor combustion (soot).
- Outdated burners and controls.
- The boiler room log(s), including boiler operations and water chemistry.
- The economic viability of investments in improvements, including whether it makes better sense to replace with new or used equipment.
- The boiler load and what the boiler capacity (size) should be to avoid wasteful cycling.
Many times, what is found is a well-maintained boiler fit for investment, which only requires an updated burner or combustion control system for improving the fuel/air mix and repeatability. Retrofits are significantly less expensive than boiler replacement, but they still provide opportunities for significant fuel savings. The audit will delineate the detail, providing the basis for an informed decision.
It also is important to investigate whether the boiler has been overheating. If so, there might be problems with either the boiler’s insulation or gasketing, which could lead to damaged and unsafe equipment. Repairs are relatively nominal to correct these issues.
Conversely, signs of overheating may indicate that the boiler is seriously scaled on the water side. This can mean that the boiler needs acid cleaning, at a fairly significant cost, or that it is time to replace the boiler.
During the efficiency analysis, the auditor is checking for specific elements in the flue gas, which indicate the effectiveness of the burner to efficiently oxidize the fuel. Additionally, the auditor is looking for the level of nitrogen oxides (a precursor to smog formation) and the stack temperature above the saturated steam temperature within the pressure vessel. Results could lead to recommending an oxygen sensor/transmitter in the exhaust gas. This device continuously senses oxygen content and provides a signal to the controller to trim the air damper or fuel valve to maintain consistent oxygen concentration as atmospheric conditions vary, thereby improving combustion efficiency. If the nitrogen oxide level is high and the boiler is in a non-attainment area for ozone (smog), a flue gas recirculation (FGR) system may be recommended and retrofitted to bring the boiler package into air quality compliance.
If the stack temperature is high, it may mean that the boiler is scaled or sooted, inhibiting proper heat transfer. A cleaning and re-tuning of the burner will, in most cases, alleviate this problem, bringing the boiler/burner package back to an acceptable fuel-to-steam efficiency.
A high stack temperature also may indicate that the boiler is an excellent candidate for a feedwater economizer, thereby reducing the stack temperature. The feedwater economizer also can increase the boiler’s efficiency by transferring BTUs in the stack to usable energy in the boiler’s feedwater makeup.
An audit also will observe and determine if it is possible to reduce the boiler’s operating pressure. The auditors look at the heating process and the existing piping layout to determine if the diameter of the piping, controls, steam traps and control valves can tolerate lower pressure. If the pressure can be reduced, fewer BTUs per hour will be used, cutting the user’s energy costs.
In addition, a complete facility audit will review the piping conditions and feedwater system, checking the steam piping for energy loss through radiation and steam leaks. Steam loss through radiation can be reduced by insulating the pipes and associated valving.
An auditor also will investigate the feedwater supply to the boiler and condensate returns. The object is to determine if water sent directly into the boiler is free of dissolved gases such as oxygen and carbon dioxide, which can cause destructive corrosion to the boiler and condensate lines. If such gases are present, the auditor may recommend installing a deaerator. Deaerators are an option if the boiler operates at 75 psig or greater, has limited standby capacity and is using 25 percent or more cold water makeup. It will greatly reduce the need for chemical treatment, which not only adds operational cost because of the cost of the chemical, but fuel cost as well.
Auditors also will examine the condensate return system and how much (hot) condensate is being returned to the boiler’s feed tank. It takes less heat to turn condensate back into steam because it returns with much of its sensible energy. Returning more condensate back to the boiler can, therefore, lead to hundreds of thousands of dollars in annual savings because the burner does not have to add as much (fuel) energy to bring the boiler water back to the boiling point.
Finally, steam trap audits typically are performed during a complete facility site audit. Besides finding, documenting and testing the individual traps, the examiners primarily look for traps that are “blowing through,” or pressurizing the condensate line(s). This can cause water logging of the heat user, which cuts efficiency and performance. This situation also can result in excessive venting and energy loss through the condensate receiver/boiler feedwater tank.
The other critical steam trap issue auditors look for is water hammer, which occurs when steam condenses in a horizontal section of the steam piping. This usually is caused by a poor condensate drainage and trapping strategy. Steam picks up the water as it travels approximately 10 times faster above the fluid, forming a wave or “slug,” which it hurls at high velocity into a pipe elbow or other restrictive device (valve, tee, etc.). This creates the characteristic loud hammering noise while severely stressing the pipe. In some cases, there is sufficient force to fracture the pipe, causing the condensate to flash into steam and expanding more than 1,600 times its volume, which can result in major damage for anything in its destructive path.
The last key component of a steam audit is what can be expected: return on investment. The boiler room or full facility audit will document where the key energy losses are occurring and what can be done to rectify the problem, returning thousands of dollars to the customer in the form of fuel burning savings. Then, given the cost of the “fix,” the installation costs and the possible (cost) loss due to downtime, the auditor and/or installing contractor can evaluate and document the ROI, fitting those retrofits which make good economic sense into the customer’s budget or time span for return of the investment.